216
System Manual SCK Gas Sampling System
42/23-81 EN Rev. 4
Touchscreen error displays
The touchscreen on the front of the control cabinet displays error messages. All
error messages do not appear directly on the touchscreen's Start screen but are
rather stored in the logbook (Message screen). Touch the
Message
button on the
interface to display this logbook.
You can display additional information in order to identify errors in detail as follows:
Step Procedure
1
Press the
Message
button on the touchscreen.
2
Select message using the scroll buttons.
3
Press
Help
button.
4
The touchscreen displays additional details.
Note:
Use the scroll buttons to view longer texts.
The following table describes errors that may occur on the gas sampling system
and measures to be taken to remedy them:
Error
display
Plain text (not stored
in controller)
Cause Measures
Stör Error
One or several pending error
messages
Rectify single error message
Faulty Entry:
___
Value input error
The value input is great-
er/less than the limits de-
fined by the system
Observe tolerance ranges
when entering values, see
De-
fault operating parameter set-
tings
on page 50
Emergency
Stop Active
EMERGENCY STOP
activated
The
EMERGENCY-STOP
switch was pressed
Find reason for activating the
EMERGENCY STOP
Remove
danger
Unlock
EMERGENCY-STOP
switch
Press service switch
WARNING!
Actuating the
service switch moves the
probe out of the kiln.
Do not
stand in the area of travel of
the probe or probe carriage.
Protection
Area OPEN
Protection area is not
closed
Personnel protection area is
not closed
Close the protection area
Check switching contact
If the contact is not used,
check the jumper
Compressed
Air Not OK
Central compressed-
air supply input pres-
sure too low
Central
compressed-air
supply disrupted
Pressure switch 577 error
Check central compressed-air
supply
Check functioning and setting
of pressure switch 577
Error display
Additional
information
Measures
Summary of Contents for SCK
Page 2: ......
Page 16: ......
Page 36: ......
Page 54: ......
Page 110: ......
Page 222: ......
Page 232: ......
Page 235: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 235 ...
Page 236: ...236 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Electrical connection plan ...
Page 237: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 237 ...
Page 238: ...238 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Transformer connection plan ...
Page 242: ......
Page 243: ......