Table 13:
Rotor injection and IED connection X81
No
Signal
1
Block injection, 220V binary in
2
Block injection, 110V binary in
3
Block injection, 48V binary in
4
Block injection, Common binary in
5
Injection Blocked NC binary out
6
Voltage/Current Saturation NO binary out
7
Common binary out
8
Voltage A, analog out
9
Voltage B analog out
10
Current A analog out
11
Current B analog out
12
Voltage sense A
13
Voltage sense B
14
Current sense A (same as 16)
15
Current sense B
16
Current sense A (same as 14)
17
-
18
-
Table 14:
Rotor injection connection X82
No
Signal
1
Injection (same as 3)
2
Injection, inside shunt resistor
3
Injection (same as 1)
4
Injection return (same as 5)
5
Injection return (same as 4)
Connect each signal connector terminal of screw compression type with one 0.5 to
2.5 mm
2
wire or with two 0.5 to 1.0 mm
2
wires.
Grounding (PE), protective earth is a separate 4 mm screw terminal, as a part of the
metallic chassis.
Section 5
1MRK 502 029-UEN A
Installing the IED
72
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...