After completion of the calibration step
•
Before leaving the ICT Tool
10.7
Auditing
During installations, calibrations and commissions the ICT generates reports for
each of the steps and collects them under the Auditing tab. See the procedures
below on how to view and delete reports as well as generate logs from reports.
1.
To view the reports, go to the
Auditing
tab.
IEC11000049-1-en.vsd
GUID-8348F60B-9BF5-4018-9740-0FA3371B0F9F V1 EN
Figure 72:
Auditing tab
2.
Open and view each report.
3.
View reports in one of the following ways:
•
In the short cut menu, right click and select
View report
.
•
Click the
View report
button in the upper right corner of the auditing
screen.
•
Double click a report record.
4.
Delete reports in one of the following ways:
•
In the short cut menu, right click and select
Delete report
.
•
Click the
Delete report
button in the upper right corner of the auditing
screen.
•
Select a record with the mouse cursor then press the Delete key on the
keyboard.
5.
Generate logs in one of the following ways:
Section 10
1MRK 502 029-UEN A
Calibrating injection based sensitive rotor earth fault protection
116
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...