Self-supervision summary = INT--FAIL and INT--WARNING
•
CPU-module status summary = INT--NUMFAIL and INT--NUMWARN
When an internal fault has occurred, extensive information about the fault can be
retrieved from the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, when it is
full, the oldest event is overwritten. The list cannot be cleared and its content
cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other
activities, such as change of settings, clearing of disturbance reports, and loss of
external time synchronization.
The information can only be retrieved from the Parameter Setting software
package. The PC can be connected either to the port at the front or at the rear of the
IED.
These events are logged as internal events.
Table 32:
Events available for the internal event list in the IED
Event message:
Description
Generating signal:
INT--FAIL
Off
Internal fail status
INT--FAIL (reset event)
INT--FAIL
INT--FAIL (set event)
INT--WARNING
Off
Internal warning status
lNT--WARNING (reset event)
INT--WARNING
lNT--WARNING (set event)
INT--NUMFAIL
Off
Numerical module fatal error
status
INT--NUMFAIL (reset event)
INT--NUMFAIL
INT--NUMFAIL (set event)
INT--NUMWARN
Off
Numerical module non-fatal
error status
INT--NUMWARN (reset
event)
INT--NUMWARN
INT--NUMWARN (set event)
IOn--Error
Off
In/Out module No. n status
IOn--Error (reset event)
IOn--Error
IOn--Error (set event)
ADMn-Error
Off
Analog/Digital module No. n
status
ADMn-Error (reset event)
ADMn-Error
ADMn-Error (set event)
MIM1-Error
Off
mA-input module status
MIM1-Error (reset event)
MIM1-Error
MIM1-Error (set event)
INT--RTC
Off
Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC
INT--RTC (set event)
Table continues on next page
1MRK 502 029-UEN A
Section 18
Fault tracing and repair
241
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...