IEC09000357-1-en.vsd
IEC09000357 V1 EN
Figure 63:
Select the TCP/IP protocol and open Properties
4. Select
Use the following IP address
and define
IP address
and
Subnet mask
if
the front port is used and if the
IP address
is not set to be obtained
automatically by the IED, see
. The IP address must be different from
the IP address chosen for the IED.
IEC09000658-1-en.vsd
IEC09000658 V1 EN
Figure 64:
Select: Use the following IP address
5. Use the
ping
command to verify connectivity with the IED.
6. Close all open windows and start PCM600.
Section 8
1MRK 502 029-UEN A
Set up the PCM600 communication link per IED
100
Installation and commissioning manual