15.2.6
Releasing the function to be tested
Release or unblock the function to be tested. This is done to ensure that only the
function or the chain of functions to be tested are in operation and that other
functions are prevented from operating. Release the tested function(s) by setting
the corresponding
Blocked
parameter under Function test modes to
No
in the local
HMI.
When testing a function in this blocking feature, remember that not only the actual
function must be activated, but the whole sequence of interconnected functions
(from measuring inputs to binary output contacts), including logic must be
activated. Before starting a new test mode session, scroll through every function to
ensure that only the function to be tested (and the interconnected ones) have the
parameters
Blocked
and eventually
EvDisable
set to
No
and
Yes
respectively.
Remember that a function is also blocked if the BLOCK input signal on the
corresponding function block is active, which depends on the configuration. Ensure
that the logical status of the BLOCK input signal is equal to 0 for the function to be
tested. Event function blocks can also be individually blocked to ensure that no
events are reported to a remote station during the test. This is done by setting the
parameter
EvDisable
to
Yes
.
Any function is blocked if the corresponding setting in the local
HMI under
Main menu/Test/Function test modes
menu remains
On
, that is, the parameter
Blocked
is set to
Yes
and the parameter
TestMode
under
Main menu/Test/IED test mode
remains active.
All functions that were blocked or released in a previous test mode
session, that is, the parameter
Test mode
is set to
On
, are reset when
a new test mode session is started.
Procedure
1.
Click the
Function test modes
menu.
The Function test modes menu is located in the local HMI under
Main menu/
Test/Function test modes
.
2.
Browse to the function instance that needs to be released.
3.
Set parameter
Blocked
for the selected function to
No
.
15.2.7
Disturbance report
15.2.7.1
Introduction
The following sub-functions are included in the disturbance report function:
Section 15
1MRK 502 029-UEN A
Verifying settings by secondary injection
152
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...