Checking the re-trip with current check,
RetripMode = CB Pos Check
1.
Set
RetripMode
=
CB Pos Check
.
2.
Apply the fault condition, including start of CCRBRF, well above the set
current value.
3.
Verify that re-trip is achieved after set time
t1
and back-up trip after time
t2
4.
Apply the fault condition, including start of CCRBRF, with current below set
current value.
5.
Verify that no re-trip, and no back-up trip is obtained.
6.
Disconnect AC and START input signals.
Checking re-trip without current check,
RetripMode = No CBPos Check
1.
Set
RetripMode
=
No CBPos Check
.
2.
Apply the fault condition, including start of CCRBRF, well above the set
current value.
3.
Verify that re-trip is achieved after set time
t1
, and back-up trip after time
t2
.
4.
Apply the fault condition, including start of CCRBRF, with current below set
current value.
5.
Verify that re-trip is achieved after set time
t1
, but no back-up trip is obtained.
6.
Disconnect AC and START input signals.
15.6.8.5
Verifying the back-up trip mode
In the cases below it is assumed that
FunctionMode
=
Current
is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1.
Apply the fault condition, including start of CCRBRF, with phase current
well above set value
IP
.
2.
Arrange switching the current off, with a margin before back-up trip time,
t2
.
It may be made at issue of re-trip command.
3.
Check that re-trip is achieved, if selected, but no back-up trip.
4.
Disconnect AC and START input signals.
The normal mode
BuTripMode
=
1 out of 3
should have been verified in the tests
above. In applicable cases the modes
1 out of 4
and
2 out of 4
can be checked.
Choose the mode below, which corresponds to the actual case.
Checking the case
BuTripMode = 1 out of 4
It is assumed that the earth-fault current setting
IN>
is below phase current setting
IP>
.
Section 15
1MRK 502 029-UEN A
Verifying settings by secondary injection
182
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...