5.5.2
Connecting injection unit REX060, coupling capacitor unit
REX061 and shunt resistor unit REX062
The figures below show typical installations for rotor and stator earth fault
protection, where injection unit REX060, coupling capacitor unit REX061 and with
and without shunt resistor unit REX062.
The injection unit REX060 should be installed close to the IED in the same
cubicle, in any case within 10 m distance of the IED.
The shunt resistor unit, REX062, should preferably also be installed in the same
cubicle, if used in the application.
Cable length between REX060 and generator should preferable not exceed 75 m, in
any case not exceed 150 m. The recommended cable area for distances up to 75 m
is 2.5 mm
2
. The cable area should be increased to 4 mm
2
for distances between 75
m and 150 m.
Cable length between REX062 and generator should preferable not exceed 75 m, in
any case not exceed 150 m. The recommended cable area for distances up to 75 m
is 2.5 mm
2
. The cable area should be increased to 4 mm
2
for distances between 75
m and 150 m.
IEC11000224.ai
IEC11000224 V1 EN
Figure 46:
Rotor connection example
1MRK 502 029-UEN A
Section 5
Installing the IED
69
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...