HVC
‐
PD
E
‐
Bus
Charger
Installation
Guide
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022 Page
79
of
146
Interlock cable connection in
secondary 1
HVC 150S
:
A Terminal
block
B Interlock cable from/to primary HVC 150
1. Move the cables towards the terminal block (A).
2. Strip 0.43 inch of the insulation from the ends of
only the White and Brown wire!
3. Crimp a ferrule onto the end of the White and Brown wire.
4. Ensure that the unused wires, the Green and Yellow wire, are protected so that they
cannot touch metal parts.
5. Make a wire connection between pin X286-6 and X286-7 and pin X286-10 and X286-11.
6. Loosen the connector screws.
7. Insert the wires into the connectors, see table below:
Functional description
Connector
Wire number
Interlock In (primary HVC 150)
X286-14
Brown
Interlock Out (primary HVC 150)
X286-15
White
Interlock GND (primary HVC 150)
X286
Shield
Interlock loop
X286-6
Black
Interlock loop
X286-7
Black
Interlock loop
X286-10
Black
Interlock loop
X286-11
Black
See also Appendix H
Signal connection diagram
.
8. Tighten the connector screws with a tightening torque of 1.0 ft-lb.