HVC
‐
PD
E
‐
Bus
Charger
Installation
Guide
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022 Page
52
of
146
4.4.5. Cable specification list
Tables below provides general specifications for the needed cables. Use these tables to select
cables, taking into account local installation conditions, cable length, cable temperature rating,
losses and local regulations.
AC and DC power cables
Functional description
DC Power cable
GND cable
AC utility power cable
Number of cores
1
1
4
Cross section
350 – 600 MCM
2 AWG
14 AWG
Min – Max external
diameter to fit through
gland
0.75 – 1.10 Inch
0.51 – 0.83 Inch
0.20 – 0.39 Inch
Shielding
No
No
No
Conductor
Tinned copper or
aluminum conductor, fine
wire
stranded acc. to VDE
0295 cl.5/IEC Cl.5
Fine strand copper wire
acc. to VDE 0295 Cl. 5/
IEC 60228 Cl. 5
Bare copper, fine wired,
bunch stranded acc. to
VDE 0295 Cl.5/IEC Cl.5
Insulation
Special rubber or PVC
(outdoor use, UV-
protected, oil resistant)
Special PVC (outdoor
use, UV-protected, oil
resistant)
Special PVC (outdoor
use, UV-protected, oil
resistant)
Nominal Voltage Uo/U
600/1000 Vac
900/1500 Vdc
450/750 Vac
450/750 Vac
Test Voltage
6 kV
4 kV
4 kV
Ambient Temperature
range
-40ºC to 80ºC,
permissible conductor
operating
tempe90°C
-40ºC to 70ºC
-40ºC to 80ºC
Core identification
gn/ye
Color Acc. to IEC 60446
Data cables
Functional description
Interlock cable
CAN cable
Number of (twisted) pairs
2 x 2
1 x 2
Cross section
18 – 14 AWG
20 – 18 AWG
Min – Max external diameter to fit
through gland
0.20 – 0.39 Inch
inapplicable
Shielding
Yes (tinned copper braid)
Yes (tinned copper braid)
Conductor
Fine strand copper wire
Fine strand copper wire
Insulation
PVC or other material that can be
used outdoor and are UV-
protected
PVC or other material that can be
used outdoor and are UV-
protected
Test Voltage
1.5 kV
1.5 kV
Ambient Temperature range
-40ºC to 70ºC
-40ºC to 70ºC
Core identification
Acc. to DIN 47100
Acc. to DIN 47100
Important: all cables must be resistant to being placed in the ground, submerged in
conduit.
All cables must have and isolation that are self-extinguishing and flame retardant
according to UL VW-1, CSA FT1.
All cables must meet the UL and the RoHS compliance.
The identity and/or function must be marked on every 78.74 Inch of the cables and
on both ends.