Communication profiles 91
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown in the state machine on page
93
.
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
RDY_RUN
1
READY TO OPERATE.
0
OFF1 ACTIVE.
2
RDY_REF
1
OPERATION ENABLED.
0
OPERATION INHIBITED.
3
TRIPPED
1
FAULT.
0
No fault.
4
OFF_2_STA
1
OFF2 inactive.
0
OFF2 ACTIVE.
5
OFF_3_STA
1
OFF3 inactive.
0
OFF3 ACTIVE.
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED.
0
–
7
ALARM
1
Warning/Alarm.
0
No warning/alarm.
8
AT_
SETPOINT
1
OPERATION.
Actual value equals
reference = is within tolerance limits, ie, in
speed control, speed error is 10% max. of
nominal motor speed.
0
Actual value differs from reference = is
outside tolerance limits.
9
REMOTE
1
Drive control location: REMOTE (EXT1 or
EXT2).
0
Drive control location: LOCAL.
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...