Start-up 53
5106 FB PAR 6
(OUTPUT INSTANCE)
23
Selects the ODVA extended speed
and torque control output instance.
5108 FB PAR 8
(INPUT INSTANCE)
73
Selects the ODVA extended speed
and torque control input instance.
5110 FB PAR 10
(ODVA SPEED SCALE)
128
Sets the scaling as 1 rpm for the
ODVA speed reference.
5111 FB PAR 11
(ODVA TORQUE SCALE)
128
Sets the scaling as 1 Nm for the
ODVA torque reference.
51.27 FBA PAR REFRESH
1
= REFRESH
Validates the FDNA-01
configuration parameter settings.
1001 EXT1 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1003 DIRECTION
3
= REQUEST
Allows control of rotation direction.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus reference 1 as
the source for speed reference.
1604 FAULT RESET SEL
8
= COMM
Selects the fieldbus interface as
the source for the fault reset
signal.
9904 MOTOR CTRL MODE
2
= VECTOR:
TORQ
Selects the vector control mode as
the motor control mode.
1002 EXT2 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
1102 EXT1/EXT2 SEL
1
= DI1
Selects digital input DI1 as the
source for the external control
location EXT1/EXT2 selection.
1106 REF2 SELECT
8
= COMM
Selects the fieldbus reference 2 as
the source for torque reference.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
1)
Read-only or automatically detected/set
Drive parameter
Setting for
ACS355 drives
Description
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...