Communication protocol 105
The format of the input assembly is:
Basic speed and torque control
plus drive parameters assembly
The Basic speed and torque control plus drive parameters
assembly, defined by ABB, adds configurable drive parameters to
the Basic speed and torque control assembly of the ODVA AC/DC
drive profile.
The format of the output assembly is:
Instance 72
Byte Bit 7
Bit 6
Bit 5
Bit 4 Bit 3 Bit 2
Bit 1
Bit 0
0
Run-
ning1
(Fwd)
Faulted
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)
Instance 122
Byte Bit 7
Bit 6
Bit 5 Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault
Reset
Run
Fwd
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference (Low Byte)
5
Torque Reference (High Byte)
6
DATA OUT 1 Value (Low Byte)
7
DATA OUT 1 Value (High Byte)
8
DATA OUT 2 Value (Low Byte)
9
DATA OUT 2 Value (High Byte)