60 Start-up
Parameter setting examples – ACS850 and ACQ810
ABB Drives profile
The following example shows how to configure the ACS850 or
ACQ810 drive to use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for
ACS850/ACQ810
drives
Description
50.01 Fba enable
1
= Enable
Enables communication between
drive and adapter module.
50.04 Fb ref1 modesel
Speed
Selects speed as the adapter
module ref1 type.
50.05 Fb ref2 modesel
Torque
Selects torque as the adapter
module ref2 type (only with
ACS850).
51.01 Fba type
DEVICENET
1)
Displays the type of the adapter
module.
51.02 FBA par2
(MAC ID)
5
Defines the MAC ID number of the
adapter module.
51.03 FBA par3
(BAUD RATE)
0
(= 125 kbit/s)
Sets the baud rate for the
DeviceNet interface.
51.06 FBA par6
(OUTPUT INSTANCE)
902
Selects the ABB Drives profile with
speed and torque plus drive
parameters output instance.
51.07 FBA par7
(OUTPUT NUM PARS)
10
Must always be set to 10, except as
provided in
Appendix A – Varying
the number of drive parameters
.
51.08 FBA par8
(INPUT INSTANCE)
952
Selects the ABB Drives profile with
speed and torque plus drive
parameters input instance.
51.09 FBA par9
(INPUT NUM PARS)
10
Must always be set to 10, except as
provided in
Appendix A – Varying
the number of drive parameters
.
52.01 FBA data in1
123
Motor power
52.02 FBA data in2
0
Motor power - LSW
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...