66 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for
ACS880 drives
Description
50.01 FBA A enable
1
= Enable
Enables communication between
drive and adapter module.
50.04 FBA A ref1 type
4
= Speed
Selects speed as the fieldbus A
reference 1 type.
50.05 FBA A ref2 type
3
= Torque
Selects torque as the fieldbus A
reference 2 type.
51.01 FBA type
DeviceNet
1)
Displays the type of the adapter
module.
51.02 MAC ID
6
Defines the MAC ID number of the
adapter module.
51.03 Baud rate
0
= 125kbit/s
Sets the baud rate for the DeviceNet
interface.
51.06 Output instance
902
Selects the ABB Drives profile with
speed and torque plus drive
parameters output instance.
51.07 Output num pars
10
Must always be set to 10. For
exceptions, see
Appendix A –
Varying the number of drive
parameters
.
52.01 FBA data in1
1.7
Motor current - MSW
52.02 FBA data in2
0
= None
Motor current - LSW
52.03 FBA data in3
1.11
DC voltage - MSW
52.04 FBA data in4
0
= None
DC voltage - LSW
52.05 FBA data in5…
52.10 FBA data in10
0
= None
53.01 FBA data out1
23.12
Acceleration time - MSW
53.02 FBA data out2
0
= None
Acceleration time - LSW
53.03 FBA data out3
23.13
Deceleration time - MSW
53.04 FBA data out4
0
= None
Deceleration time - LSW
53.05 FBA data out5…
53.10 FBA data out10
0
= None
51.27 FBA par refresh
1
= Configure
Validates the FDNA-01 configuration
parameter settings.
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...