108 Communication protocol
Extended speed and torque control assembly
The Extended speed and torque control assembly is defined by the
ODVA AC/DC drive profile. The format of the output assembly is:
The format of the input assembly is:
Instance 23
Byte Bit 7
Bit 6
Bit 5
Bit 4 Bit 3 Bit 2
Bit 1
Bit 0
0
NetRef NetCtrl
Fault
Reset
Run
Rev
Run
Fwd
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference (Low Byte)
5
Torque Reference (High Byte)
Instance 73
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At
Refer-
ence
Ref
From
Net
Ctrl
From
Net
Ready Run-
ning2
(Rev)
Run-
ning1
(Fwd)
Warn-
ing
Faulted
1
Drive State (See section
State (Control supervisor object)
.
)
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Torque Actual (Low Byte)
5
Torque Actual (High Byte)