52 Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
47Eh (1150 decimal) –> READY TO SWITCH ON
•
47Fh (1151 decimal) –> OPERATING (Speed mode)
or
C7Fh (3199 decimal) –> OPERATING (Torque mode).
ODVA AC/DC drive profile
The following example shows how to configure the ACS355 drive
to use the Extended speed and torque control assembly of the
ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
The table below gives the recommended drive parameter settings.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus interface as the
source for the inverted Run enable
signal (Run disable).
1)
Read-only or automatically detected/set
Drive parameter
Setting for
ACS355 drives
Description
9802 COMM PROT SEL
4
= EXT FBA
Enables communication between
drive and adapter module.
5101 FBA TYPE
DEVICENET
1)
Displays the type of the adapter
module.
5102 FB PAR 2
(MAC ID)
5
Defines the MAC ID number of the
adapter module.
5103 FB PAR 3
(BAUD RATE)
0
(= 125 kbit/s)
Sets the baud rate for the
DeviceNet interface.
5104 FB PAR 4
(DRIVE PROFILE)
0
(= DCU Profile)
Selects the profile used in the
communication between drive and
adapter module.
5105 FB PAR 5
(ODVA STOP FUNC)
0 (
= Ramp)
Motor decelerates along the active
deceleration ramp.
Drive parameter
Setting for
ACS355 drives
Description
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...