42 Start-up
11
ODVA TORQUE
SCALE
Defines the torque scale in the ODVA AC/DC
drive profile. Units of reference and actual
torques for the ODVA AC/DC drive profile are
given by the formula below. No effect on the
ABB Drives profiles.
Note:
While a wide range of resolutions may be
configured, the actual performance is limited to
the performance capabilities of the drive.
(N·m = Newton x Meter)
Torque unit = N·m x 2
(-1 X ODVA torque scale)
128
ACS355:
FB PAR 11
ACSM1:
FBA PAR11
ACS850/ACQ810:
FBA par11
ACS880:
ODVA torque
scale
Table below shows how the values of drive
parameter ODVA TORQUE SCALE correspond
to the ODVA Torque Scale units.
123
…
133
Torque scale value of the drive parameter
12
…
25
Reserved
Not used by the adapter module.
N/A
No.
Name/Value
Description
Default
ODVA torque scale value
1)
Torque scale value of
drive parameter
2)
Unit
-5
123
32 N·m
-4
124
16 N·m
-3
125
8 N·m
-2
126
4 N·m
-1
127
2 N·m
0 (default)
128
1 N·m
1
129
0.5 N·m
2
130
0.25 N·m
3
131
0.125 N·m
4
132
0.0625 N·m
5
133
0.03125 N·m
1)
Use the ODVA torque scale value when reading/writing parameter
ODVA
TORQUE SCALE
via
AC/DC-drive object, class 2Ah
. When written via the
AC/DC drive object, the new value takes effect immediately.
2)
Use the torque scale value of the drive parameter when reading/writing
parameter
ODVA TORQUE SCALE
via the drive control panel,
Drive
parameter object, Class 90h
and
Fieldbus configuration object 91h
. When
written via these methods, the new value takes effect after the drive is
repowered or a “Fieldbus Adapter Parameter refresh” is given.
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...