Start-up 65
Starting up ACS880 drives
This example sets up the fieldbus adapter installed as fieldbus
adapter A. To set up the fieldbus adapter B, perform the same
tasks with the corresponding parameters in parameter groups 50,
54, 55, and 56.
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA A enable to Enable.
3. Ensure that parameter 50.04 FBA A ref1 type is set to Speed
and parameter 50.05 FBA A ref2 type is set to Torque.
4. Set the FDNA-01 configuration parameters in drive parameter
group 51.
5. Define the process data transferred to and from the drive in
FDNA-01 parameter groups 52 and 53.
Note:
If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through
Fieldbus configuration object 91h
.
6. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA par refresh to Refresh.
7. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACS880
ABB Drives profile
The following example shows how to configure the ACS880 drive
to use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...