68 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for
ACS880 drives
Description
50.01 FBA A enable
1
= Enable
Enables communication between
drive and adapter module.
50.04 FBA A ref1 type
4
= Speed
Selects Speed as the fieldbus A
reference 1 type.
50.05 FBA A ref2 type
3
= Torque
Selects Torque as the fieldbus A
reference 2 type.
51.01 FBA type
DeviceNet
1)
Displays the type of the adapter
module.
51.02 MAC ID
6
Defines the MAC ID number of the
adapter module.
51.03 Baud rate
0
= 125kbit/s
Sets the baud rate for the DeviceNet
interface.
51.06 Output instance
23
Selects the ABB Drives profile with
speed and torque plus drive
parameters output instance.
51.07 Output num pars
10
Must always be set to 10. For
exceptions, see
Appendix A –
Varying the number of drive
parameters
.
51.27 FBA par refresh
1
= Configure
Validates the FDNA-01 configuration
parameter settings.
19.11 Ext1/Ext2 selection
3
= DI1
Selects digital input DI1 as the
source for the external control
location EXT1/EXT2selection.
19.12 Ext1 control mode 1
2
= Speed
Selects speed control as the control
mode 1 for external control location
EXT1.
19.14 Ext2 control mode 1
3
= Torque
Selects torque control as the control
mode 1 for external control location
EXT2.
20.01 Ext1 commands
12
= Fieldbus A
Selects fieldbus interface A as the
source of the start and stop
commands for external control
location EXT1.
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...