164 Appendix A – Varying the number of drive parameters
is provided below. For manual configuration, see the
documentation for the DeviceNet master.
Note:
Only one EDS file with the same Product ID can be installed
at a time. Changing the EDS file changes it for all drives with that
Product ID. In situations where it is necessary to have different
sizes of the same assembly on devices with the same Product ID,
manual configuration is required.
The number of drive parameters may be configured between one
and ten for output and input by changing the configuration value of
parameters
07
OUTPUT NUM PARS
or
09
INPUT NUM PARS
respectively. To use zero drive parameters, use the assembly upon
which the "plus drive parameters" assembly is based.
To change the EDS file, copy it to a new file name and open the
copy with a text editor. Search for the [IO_Info] section of the file
for the appropriate assembly. For example, the entry for the Basic
speed control input plus drive parameters is below.
The length in bytes needs to be updated to match the value from
the table below. If more than one assembly "plus drive parameters"
is being used, both assembly entries in the file must be changed.
The assembly entries must be changed in all the "plus drive
parameters" assemblies needing a custom number of parameters.
Save the file. Use the new EDS file to configure the DeviceNet
master.
Input7=
24, 0, 0x0005,
Basic speed control input + drive parameters",
7, "20 04 24 AA 30 03",
"Basic speed control input + drive parameters";
Length in bytes
Summary of Contents for FDNA-01
Page 2: ...List of related manuals See section Related manuals on page 16 ...
Page 4: ......
Page 14: ...14 Safety ...
Page 22: ...22 About the manual ...
Page 32: ...32 Electrical installation ...
Page 72: ...72 Start up 3 Configure the device MAC address ...
Page 76: ...76 Start up ...
Page 96: ...96 Communication profiles ...
Page 154: ...154 Communication protocol ...
Page 162: ...162 Technical data ...
Page 166: ...166 Appendix A Varying the number of drive parameters ...