Faults and Alarms
15-18
15
P0810 – Temperature V-B4/IGBT V4
P0811 – Temperature W-B4/IGBT W4
P0812 – Temperature U-B5/IGBT U5
P0813 – Temperature V-B5/IGBT V5
P0814 – Temperature W-B5/IGBT W5
Adjustable
Range:
-20.0 °C to 150.0 °C
Factory
Setting:
Properties:
RO
Access groups
via HMI:
01 PARAMETER GROUPS
or
09 READ ONLY PARAMETERS
45 Protections
Description:
These reading parameters indicate, in Celsius degrees (ºC), the internal temperature of the IGBTs of each phase. In
a modular drive, this information is shown for each Book, and in case of frame H it is shown for each IGBT module.
P0832 - Digital Input DIM1 Function
P0833 - Digital Input DIM2 Function
Adjustable
Range:
0 = Not Used
1 = No External Fault IPS
2 = No Refrigeration Fault
3 = No Braking Overtemperature Fault
4 = No External Rectifier Overtemperature Fault
5 = No External Rectifier Temperature Alarm
6 = No External Rectifier Fault
Factory
Setting:
0
Properties:
CFW-11M
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
45 Protections
40 Digital Inputs
Description:
These parameters allow configuring the digital inputs DIM1 and DIM2 for the type of fault (1, 2, 3, 4 or 6) or alarm
(5) to be detected. The fault or alarm code will be displayed on the HMI, and the inverter will be disabled when the
selected fault occurs.
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...