Functions Common to All the Control Modes
12-20
12
P0299 - DC-Braking Start Time
Adjustable
Range:
0.0 to 15.0 s
Factory
Setting:
0.0 s
Properties:
V/f, VVW and Sless
Access groups
via HMI:
01 PARAMETER GROUPS
47 DC Braking
Description:
This parameter sets the DC braking time at starting.
INJECTION OF DIRECT
CURRENT AT STARTING
Motor Speed
Time
DC Braking
Run
Stop
P0299
P0302/P0372
(V/f, VVW)/(Sensorless)
Time
Figure 12.10 -
DC braking operation at starting
P0300 – DC-Braking Stop Time
Adjustable
Range:
0.0 to 15.0 s
Factory
Setting:
0.0 s
Properties:
V/f, VVW and Sless
Access groups
via HMI:
01 PARAMETER GROUPS
47 DC Braking
Description:
This parameter sets the DC braking time at stopping.
The
presents the DC braking operation via ramp disabling (refer to P0301).