Quick Parameter Reference, Faults and Alarms
0-33
0
Fault/Alarm
Description
Possible Causes
A138
(5)
Profibus DP Interface in
Clear Mode
It indicates that the inverter received a command
from the Profibus DP network master to enter the
clear mode.
Verify the network master status, making sure it is in
execution mode (Run).
Refer to the Profibus DP communication manual for more
information.
A139
(5)
Offline Profibus DP
Interface
It indicates an interruption in the communication
between the Profibus DP network master and the
inverter.
Verify whether the network master is correctly configured
and operating normally.
Verify the network installation in a general manner - cable
routing, grounding.
Refer to the Profibus DP communication manual for more
information.
A140
(5)
Profibus DP Module
Access Error
It indicates an error in the access to the Profibus DP
communication module data.
Verify whether the Profibus DP module is correctly fit into
the slot 3.
Refer to the Profibus DP communication manual for more
information.
F150
Motor Overspeed
Overspeed fault.
It is activated when the real speed exceeds the value
of P0134 x (100 % + P0132) for more than 20 ms.
Wrong settings of P0161 and/or P0162.
Problem with the hoist-type load.
F151
FLASH Memory Module
Fault
FLASH Memory Module fault (MMF-01).
Defective FLASH memory module.
Check the connection of the FLASH memory module.
A152
Internal Air High
Temperature
Alarm indicating that the internal air temperature is
too high.
Note:
It may be disabled by setting P0353 = 1 or 3.
Surrounding air temperature too high (>50 °C (122 °F))
and excessive output current.
Defective internal fan (if installed).
For the CFW-11M and the frame sizes E, F and G:
High temperature (> 45 ºC) inside the cabinet.
F153
Internal Air
Overtemperature
Internal air overtemperature fault.
A155
(12) (10)
Undertemperature
Only 1 sensor indicates temperature below -30 ºC.
Surrounding air temperature ≤ -30 °C (-22 °F).
F156
Undertemperature
Undertemperature fault (below -30 °C (-22 °F)) in
the IGBTs or rectifier measured by the temperature
sensors.
Surrounding air temperature ≤ -30 °C (-22 °F).
F160
Safety Stop Relays
Safety Stop relay fault.
One of the relays is defective or it does not have +24 V
applied to its coil.
F161
Timeout PLC11CFW-11
Refer to the PLC11-01 Module programming manual.
A162
Incompatible PLC
Firmware
A163
Break Detect AI1
It indicates that the AI1 current (4-20 mA or 20-4 mA)
reference is out of the 4 to 20 mA range.
Broken AI1 cable.
Bad contact at the signal connection to the terminal strip.
A164
Break Detect AI2
It indicates that the AI2 current (4-20 mA or 20-4 mA)
reference is out of the 4 to 20 mA range.
Broken AI2 cable.
Bad contact at the signal connection to the terminal strip.
A165
Break Detect AI3
It indicates that the AI3 current (4-20 mA or 20-4 mA)
reference is out of the 4 to 20 mA range.
Broken AI3 cable.
Bad contact at the signal connection to the terminal strip.
A166
Break Detect AI4
It indicates that the AI4 current (4-20 mA or 20-4 mA)
reference is out of the 4 to 20 mA range.
Broken AI4 cable.
Bad contact at the signal connection to the terminal strip.
F174
(6)
Left Fan Speed Fault
Heatsink left fan speed fault.
Dirt on the blades and in the bearings of the fan.
Defective fan.
Defective fan power supply connection.
F175
(7)
Center Fan Speed Fault
Heatsink center fan speed fault.
F176
(6)
Right Fan Speed Fault
Heatsink right fan speed fault.
A177
Fan Replacement
Fan replacement alarm (P0045 > 50000 hours).
Note:
This function may be disabled by setting P0354 = 0.
Maximum number of operating hours for the heatsink fan
has been reached.
F178
Heatsink Fan Speed Alarm
This alarm indicates a problem with the heatsink fan.
Dirt on the blades and in the bearings of the fan.
Defective fan.
Defective fan power supply connection.
F179
Heatsink Fan Speed Fault
This fault indicates a problem with the heatsink fan.
Note:
This function may be disabled by setting P0354 = 0.
Dirt on the blades and in the bearings of the fan.
Defective fan.
Defective fan power supply connection.
A181
Invalid Clock Value
Invalid clock value alarm.
It is necessary to set date and time at parameters P0194
to P0199.
Keypad battery is discharged, defective, or not installed.
F182
Pulse Feedback Fault
Indicates a fault on the output pulses feedback.
Defect in the inverter internal circuitry.
Inverter operating without motor.
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...