PM Vector Control
21-8
21
P0442 – Inductance Lq - CT
P0443 – Inductance Lq - CT
Adjustable
Range:
0.0 to 400.0 mH
Factory
Setting:
0.0 mH
Properties:
CFG and PM
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
Adjust them according to the motor nameplate data. If these pieces of information are not available, keep the
default value.
The view of parameters P0433, P0434, P0442 and P0443 will depend on the value set in P0430.
NOTE!
The use of the default value causes:
1. It increases the output current, because the motor in those conditions does not produce the
reluctance torque. The increase of the output current may cause increase in the motor temperature.
2. It prevents the motor operation in the field-weakening region.
P0435 – Ke Constant
Adjustable
Range:
0 to 600.0
Factory
Setting:
100.0 V/krpm
Properties:
CFG and PM
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
P0444 – Constant Ke – CT
Adjustable
Range:
0 to 3000
Factory
Setting:
100 V/krpm
Properties:
CFG and PM
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Note:
ke is the generated voltage constant. It is a characteristic of the motor, which determines the voltage generated
as a function of the motor speed. The used engineering unit is V/krpm (Volts/1000 rpm).
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...