Starting-up and Settings
7-2
7
Table 7.1 -
Parameter P0204 options
P0204
Action
0, 1
Not Used:
no action
2
Reset P0045:
resets the enabled fan hour counter
3
Reset P0043:
resets the enabled hours counter
4
Reset P0044:
resets the kWh counter
5
Load 60 Hz:
loads the 60 Hz factory settings into the inverter parameters
6
Load 50 Hz:
loads the 50 Hz factory settings into the inverter parameters
7
Load User 1:
loads the User 1 parameters into the current inverter parameters
8
Load User 2:
loads the User 2 parameters into the current inverter parameters
9
Load User 3:
loads the User 3 parameters into the current inverter parameters
10
Save User 1:
saves the current inverter parameters into the User 1 parameter memory
11
Save User 2:
saves the current inverter parameters into the User 2 parameter memory
12
Save User 3:
saves the current inverter parameters into the User 3 parameter memory
User
Memory 3
User
Memory 1
User
Memory 2
Factory
Setting
Current
inverter
parameters
P0204 = 10
P0204 = 7
P0204 = 11
P0204 = 12
P0204 = 9
P0204 = 8
P0204 = 5 or 6
Figure 7.1 -
Parameter transfer
In order to load parameters from User 1, User 2 and/or User 3 to the CFW-11 operation area (P0204 = 7, 8 or 9),
it is necessary that these areas had been saved previously.
The operation of loading one of those memories can also be performed via digital inputs (DIx). Refer to the
13.1.3 Digital Inputs [40] on page 13-12
, for more details regarding this programming (P0204 = 10, 11 or 12).
NOTE!
When P0204 = 5 or 6, the parameters P0201 (Language), P0295 (Rated Current), P0296 (Line Rated
Voltage), P0297 (Switching Frequency), P0308 (Serial Address), P0352 (Fan Control Configuration)
and P0359 (Motor Current Stab.), will not be change by the factory settings.
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...