Quick Parameter Reference, Faults and Alarms
0-36
0
Fault/Alarm
Description
Possible Causes
F322
(10)
Overtemperature at IGBT
V B3
Overtemperature fault measured with the temperature
sensor (NTC) of the book 3 V phase IGBT.
High ambient temperature
(*)
and high output current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.
A324
(10)
High Temperature at IGBT
W B3
High temperature alarm measured with the
temperature sensor (NTC) of the book 3 W phase
IGBT.
F325
(10)
Overtemperature at IGBT
W B3
Overtemperature fault measured with the temperature
sensor (NTC) of the book 3 W phase IGBT.
A327
(10)
High Temperature at IGBT
U B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 U phase
IGBT.
F328
(10)
Overtemperature at IGBT
U B4
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 U phase IGBT.
A330
(10)
High Temperature at IGBT
V B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 V phase
IGBT.
F331
(10)
Overtemperature at IGBT
V B4
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 V phase IGBT.
A333
(10)
High Temperature at IGBT
W B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 W phase
IGBT.
F334
(10)
Overtemperature at IGBT
W B4
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 W phase IGBT.
A336
(10)
High Temperature at IGBT
U B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 U phase
IGBT.
F337
(10)
Overtemperature at IGBT
U B5
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 U phase IGBT.
A339
(10)
High Temperature at IGBT
V B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 V phase
IGBT.
F340
(10)
Overtemperature at IGBT
V B5
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 V phase IGBT.
A342
(10)
High Temperature at IGBT
W B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 W phase
IGBT.
F343
(10)
Overtemperature at IGBT
W B5
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 W phase IGBT.
A345
(10)
High Load at IGBT U B1
Overload alarm at book 1 U phase IGBT.
High current at the inverter output (see figure 8.1 of the
CFW-11M user's manual).
F346
(10)
Overload at IGBT U B1
Overload fault at book 1 U phase IGBT.
A348
(10)
High Load at IGBT V B1
Overload alarm at book 1 V phase IGBT.
F349
(10)
Overload at IGBT V B1
Overload fault at book 1 V phase IGBT.
A351
(10)
High Load at IGBT W B1
Overload alarm at book 1 W phase IGBT.
F352
(10)
Overload at IGBT W B1
Overload fault at book 1 W phase IGBT.
A354
(10)
High Load at IGBT U B2
Overload alarm at book 2 U phase IGBT.
F355
(10)
Overload at IGBT U B2
Overload fault at book 2 U phase IGBT.
(*)
Temperature > 40 ºC or 45 ºC, depending on the model. Refer to the section 3.1 - Installation Environment, of the CFW-11M user's manual.
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...