13-29
13
Digital and Analog Inputs and Outputs
13.2 LOCAL AND REMOTE COMMAND
In those parameter groups one can configure the origin of the main inverter commands when in the LOCAL or
in the REMOTE situation, as the Speed Reference, Speed Direction, Run/Stop and JOG.
P0220 – LOCAL/REMOTE Selection Source
Adjustable
Range:
0 = Always LOCAL
1 = Always REMOTE
2 = Local/Remote Key LOCAL
3 = Local/Remote Key REMOTE
4 = DIx
5 = Serial/USB LOCAL
6 = Serial/USB REMOTE
7 = Anybus-CC LOCAL
8 = Anybus-CC REMOTE
9 = CANopen/DeviceNet/Profibus DP LOCAL
10 = CANopen/DeviceNet/Profibus DP REMOTE
11 = SoftPLC LOCAL
12 = SoftPLC REMOTE
13 = PLC11 LOCAL
14 = PLC11 REMOTE
Factory
Setting:
2
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
31 Local Command
32 Remote Command
Description:
It defines the origin of the command that will select between the LOCAL situation and the REMOTE situation, where:
LOCAL: Means Local Default situation.
REMOTE: Means Remote Default situation.
DIx: Refer to the
Item 13.1.3 Digital Inputs [40] on page 13-12
.
P0221 – Speed Reference Selection – LOCAL Situation
P0222 – Speed Reference Selection – REMOTE Situation
Adjustable
Range:
0 = HMI
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI1 + AI2 > 0 (Sum AIs > 0)
6 = AI1 + AI2 (Sum AIs)
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Anybus-CC
11 = CANopen/DeviceNet/Profibus DP
12 = SoftPLC
13 = PLC11
Factory
Setting:
P0221 = 0
P0222 = 1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
31 Local Command
32 Local Command
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...