PID Regulator [46]
20-14
20
P0530 – Process Variable Engineering Unit 1
P0531 – Process Variable Engineering Unit 2
P0532 – Process Variable Engineering Unit 3
Adjustable
Range:
32 to 127
Factory
Setting:
P0530 = 37
P0531 = 32
P0532 = 32
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
46 PID Regulator
Description:
The process variable engineering unit is composed of three characters, which will be applied to the indication of
the parameters P0040 and P0041. The parameter P0530 defines the left most character, P0531 the center and
P0532 the right most.
The characters that can be chosen correspond to the ASCII code 32 to 127.
Examples:
A, B, ...,
Y,
Z, a,
b,
...,
y,
z,
0,
1, ..., 9,
#,
$,
%,
(,
),
*,
+, ...
−To indicate "bar":
−To indicate "%":
P0530 = "b" (98)
P0530 = "%" (37)
P0531 = "a" (97)
P0531 = " " (32)
P0532 = "r" (114)
P0532 = " " (32)
P0533 – PVx Process Variable
P0534 – PVy Process Variable
Adjustable
Range:
0.0 to 100.0 %
Factory
Setting:
P0533 = 90.0 %
P0534 = 10.0 %
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
46 PID Regulator
Description:
Those parameters are used in the functions of the digital/relay outputs, with the purpose of signalizing/alarm, and
they will indicate:
Process Variable > VPx and
Process Variable < VPy
The values are in percentage of the process variable full scale:
P0040 =
(10)
P0529
x 100 %
P0528
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...