PM Vector Control
21-12
21
Description:
It enables or disables the Without losses function of the DC Link Regulator, according to the next table.
Table 21.1 -
DC Link Regulation Modes
P0184
Action
0 = With losses
(Optical Braking)
INACTIVE. If it is used, F022 (overvoltage) may occur during the speed reduction
1 = Without losses
Automatic control of the deceleration ramp. The Optical Braking is inactive. The deceleration ramp is
autimatically adjusted in order to keep the DC link below the level adjusted in P0185
This procedure avoid the overvoltage fault at the DC link (F022). It can also be used with accentric loads
2 = Enable/Disable via DIx
DIx = 24 V: Braking actuates as described for P0184 = 1
DIx = 0 V: The Without Losses Braking stays inactive. The DC link voltage will be controlled by the
parameter P0153 (Dynamic Braking)
P0185 – DC Link Voltage Regulation Level
P0186 – DC Link Voltage Regulation Proportional Gain
P0187 – DC Link Voltage Regulation Integral Gain
21.7.6 Flying Start/Ride-Through [44]
P0321 – DC Link Power Loss
P0322 – DC Link Ride-Through
P0323 – DC Link Power Back
P0325 – Ride-Through Proportional Gain
P0326 – Ride-Through Integral Gain
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
0.128
Properties:
PM and Vector
Access groups
via HMI:
01 PARAMETER GROUPS
44 FlyStart/RideThru
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...