Programming Basic Instructions
5-7
5
P0208 – Reference Scale Factor
Adjustable
Range:
1 to 18000
Factory
Setting:
1800
(1500)
P0212 – Reference Decimal Point
Adjustable
Range:
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
Factory
Setting:
0
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
30 HMI
Description:
They define how the Speed Reference (P0001) and the Motor Speed (P0002) will be presented when the motor runs
at the synchronous speed.
In order to indicate the value
in rpm
, P0208 must be adjusted at the motor synchronous speed according to the
:
Table 5.4 -
Synchronous speed reference in rpm
Frequency
Number of Motor Poles
Synchronous Speed in rpm
50 Hz
2
3000
4
1500
6
1000
8
750
60 Hz
2
3600
4
1800
6
1200
8
900
In order to indicate values in
other units
, use the following formulas:
P0002 = Speed x P0208
Synchronous Speed x (10)
P0212
P0001 = Reference x P0208
Synchronous Speed x (10)
P0212
Where,
Reference = Speed reference, in rpm.
Speed = Actual speed, in rpm.
Synchronous Speed = 120 x Motor Rated Frequency (P0403)/Nr. of Poles.
Nr. of Poles = 120 x P0403 / Motor Rated Speed (P0402), and can be equal to 2, 4, 6, 8 or 10.
Example:
If Speed = Synchronous Speed = 1800,
P0208 = 900,
P0212 = 1 (wxy.z), then
P
0002 =
1800
x 900 = 90.0
1800 x
(10)
1
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...