Vector Control
11-30
11
P0172 – Maximum "-" Torque Current at Maximum Speed
Adjustable
Range:
0.0 to 350.0 %
Factory
Setting:
125.0 %
Properties:
Vector
Access groups
via HMI:
01 PARAMETER GROUPS
29 Vector Control
95 Torque Curr.Limit
Description:
Torque current limitation in function of the speed:
Torque current limitation
P0170/P0169
P0172/P0171
P0173 = 0
P0173 = 1
Synchronous speed
x
P0190
P0400
P0134
n
Figure 11.5 -
Torque limitation actuation curve at maximum speed
This function stays inactive when the contents of P0171/P0172 are higher or equal to the contents of P0169/P0170.
P0171 and P0172 do also act during optimal braking limiting the maximum output current.
P0173 – Maximum Torque Curve Type
Adjustable
Range:
0 = Ramp
1 = Step
Factory
Setting:
0
Properties:
Vector
Access groups
via HMI:
01 PARAMETER GROUPS
29 Vector Control
95 Torque Curr.Limit
Description:
It defines how the actuation of the torque limitation curve will be at the field weakening region. Refer to the
11.8.7 DC Link Regulator [96]
For the deceleration of high inertia loads with short deceleration times, the CFW-11 has available the DC Link
Regulation function, which avoids the tripping of the inverter by overvoltage in the DC link (F022).
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...