10-7
10
VVW Control
Seq.
Action/Result
Display Indication
14
- If necessary, change
the content of P0400
according to the motor
rated voltage. Therefore
press "
Select
". This change
corrects the output voltage
by the factor
x = P0400/P0296.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Eff.
P0399: 67.0 %
Motor Rated Voltage
P0400: 440 V
15
- If necessary, change
the content of P0401
according to the motor
rated current. Therefore
press "
Select
". This change
will affect P0156, P0157,
P0158 and P0410.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 13.5 A
16
- If necessary, change
the content of P0402
according to the motor
rated speed. Therefore
press "
Select
". This change
will affect P0122 to
P0131, P0133, P0134,
P0182, P0208, P0288
and P0289.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Current
P0401: 13.5A
Motor Rated Speed
P0402: 1750 rpm
17
- If necessary, change
the content of P0403
according to the motor
rated frequency. Therefore
press "
Select
".
Config LOC
0rpm
Reset
13:08 Select
Motor Rated Speed
P0402: 1750 rpm
Motor Rated Frequency
P0403: 60 Hz
18
- If necessary, change
the content of P0404
according to the motor
rated power. Therefore
press "
Select
". This change
will affect P0410.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 7.5 hp
Seq.
Action/Result
Display Indication
19
- If necessary, change
the content of P0406
according to the motor
ventilation type. Therefore
press "
Select
".
This change will affect
P0156, P0157, P0158,
P0399, and P0407.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Power
P0404: 7.5 hp
Motor Ventilation
P0406: Self-Vent.
20
If necessary, change the
content of P0407 according
to the motor rated power
factor. Therefore press
"
Select
".
Config LOC
0rpm
Reset
13:48 Select
Motor Ventilation
P0406: Self-Vent.
Motor Rated Power Fac
P0407: 0.68
21
- At this point the keypad
(HMI) presents the option
for running the "
Self-
tuning
". Whenever it is
possible, one must run the
Self-tuning.
- Thus, press "
Select
" to
access the parameter
P0408 and then
to select the option "
[001]
No Rotation
". Refer to the
Item 11.8.5 Self-Tuning
[05] and [94] on page
11-23
- Next press "
Save
".
Config LOC
0rpm
Reset
13:09 Select
Motor Rated Power Fac
P0407: 0.68
Run Self-Tuning
P0408: No
Ready
LOC
0rpm
Return
13:48
Save
P0408
Run Self-Tuning
[001] No Rotation
22
- After this the Self-tuning
routine is initiated and the
"SelfTun" status is indicated
at the top left part of the
keypad (HMI).
- The keypad (HMI)
will initiate the routine
presenting "
P0409
Estimating Rs
". Wait until
the end of the Self-tuning
routine.
SelfTun LOC
0rpm
13:48
P0409
Estimating Rs
23
- Once the Self-tuning
routine has finished, the
inverter returns to the
Monitoring Mode and it is
ready to operate.
Ready
LOC
0rpm
13:48
Menu
0
rpm
0.0
A
0.0
Hz
Figure 10.2 -
VVW mode Oriented Start-up
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...