The factory setting of P0144 (8.0 %) is adequate for standard motors with rated frequency of 60 Hz. When using
a motor with rated frequency (adjusted in P0403) different from 60 Hz, the default value for P0144 may become
inadequate, being able to cause difficulties in the motor starting. A good approximation for the setting of P0144 is
given by the formula:
P0144 =
3 x P0142
P0403
If it is necessary to increase the starting torque, increase gradually the value of P0144.
Output
Voltage
Line rated voltage
100 %
P0142
P0143
P0144
0.1 Hz
3 Hz
P0146
P0145
P0134
P0202 = 2
Speed/Frequency
Figure 9.8 -
V/f curve in function of P0142 to P0146
9.3 V/F CURRENT LIMITATION [26]
P0135 – Maximum Output Current
Adjustable
Range:
0.2 to 2xI
nom-HD
Factory
Setting:
1.5xI
nom-HD
Properties:
V/f and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
26 V/f Current Limit
P0344 – Current Limitation Configuration
Adjustable
Range:
0 = Hold -FL ON
1 = Decel. -FL ON
2 = Hold -FL OFF
3 = Decel. -FL OFF
Factory
Setting:
3
Properties:
V/f, CFG and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
26 V/f Current Limit
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...