Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
97
of
100
The available parameters are used to set the warnings that indicate if the difference between
water inlet and outlet on the source heat exchanger is within certain limits. Parameter SW04
defines the warning delay from compressor start-up.
Modbus
address
Read
Write
Code
Meaning
Min
Max
Unit of
measurement
16518
RW
SW01
High source water
temperature
difference warning set point
0
30
°C
16519
RW
SW02
Low source water temperature
difference warning set point
-10
10
°C
16520
RW
SW03
Low source water temperature
difference warning
differential
0
30
°C
16827
RW
SW04
High/low source water
temperature difference from
compressor start-up warning
delay
0
1,200
sec
8.12.12. Menu - Ba Bacnet IP
On the service menu, with the BA key selected, press the OK key to access the screen used to
set the BACnet IP parameters.