Lync AEGIS Controller
3: USER OPERATION VIA WEB INTERFACE
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
32
of
100
3.1.6. User Settings
It is possible to set the unit hot water temperature via web interface in the menu
User setting
–
Hot water regulation.
Please n
ote that the “ST01 Hot Water out temperature set point” doesn’t directly influence the
compressor ON/OFF status. The delivery temperature is regulated by modulating the primary side
pump, therefore the flow of hot water at the outlet is not constant.
If the outlet temperature probe is below the set point of the pump speed is decreased, while
above set temperature ST01 is increased.
3.1.7. Double Probe
In the same menu it is possible to enable the BT1 and BT2 probes via the web interface in the
User setting
– Double probe function
menu.