Lay down the cable in dedicated cable rails, as far as possible to
power cables. In order to avoid disturbances, it has to be placed
far from sources of electrical noise:
•
Radio antennas
•
Fluorescent lights
•
Contactors and relays
•
Other magnetic field generating devices
•
Never do “star” or “branch” connections. See next picture for some
examples of correct (b-d-f) and wrong connections (a-c-e):
8.12.5. Menu - Et Ethernet
On the service menu, with the ET key selected, press the OK key to access the screen used to
set the Ethernet port.
Select the different parameters with the UP and DOWN keys. Once the parameter has been
selected, press the OK key to edit the parameter.
When the parameter is in edit mode:
•
press the UP key to increase the value;
•
press the DOWN key to decrease the value;
•
press the BACK key to select the left box;
•
press the RIGHT key to select the right box;
•
press the OK key to exit the parameter’s edit mode.
Modbus
address
Read
Write
Meaning
Min
Max
15798
RW
IP address first part
0
255
15799
RW
IP address second part
0
255
15800
RW
IP address third part
0
255
15801
RW
IP address fourth part
0
255
15802
RW
Gateway first part
0
255
15803
RW
Gateway second part
0
255
15804
RW
Gateway third part
0
255
15805
RW
Gateway fourth part
0
255