Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
94
of
100
15806
RW
Net Mask first part
0
255
15807
RW
Net Mask second part
0
255
15808
RW
Net Mask third part
0
255
15809
RW
Net Mask fourth part
0
255
15818
RW
DHCP enabling
0 = OFF
1 = ON
Reboot the controller (switch it off and back on) for the new values to take effect.
8.12.6. Menu - Df Defrost
On the service menu, with the DF key selected, press the OK key to access the screen used to
set the defrost parameters. Select the different parameters with the UP and DOWN keys. Once
the parameter has been selected, press the OK key to edit the parameter. The DF01 parameter
defines whether defrost is performed at a fixed or dynamic evaporation temperature. The
dynamic evaporation temperature mode is recommended.
8.12.7. Df01 = 0 - Defrost At A Fixed Evaporation Temperature
If DF01 = 0 the controller compares the evaporation temperature with parameter DF02. When
the evaporation temperature drops below this value, the DF06 timer begins. After the DF06 time
has elapsed, the defrost phase starts.
8.12.8. Df01 = 1 - Defrost At A Dynamic Evaporation Temperature (Default Setting)
If DF01 = 1 the controller compares the evaporation temperature with the dynamic evaporation
temperature value. When the evaporation temperature drops below this value, the DF06 timer
begins. After the DF06 time has elapsed, the defrost phase starts.