Lync AEGIS Controller
4: APPENDIX A - INTERNAL CONTROL SPECIFICATIONS & TECHNICAL DATA
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
51
of
100
Max voltage
230VMax current
2A
101 -
102
No
voltage
Dry contact for alarms
●
●
●
Max voltage
230VMax current
2A
103
–
104
No
voltage
Dry contact for signal
warning
●
●
●
Max voltage
230VMax current
2A
105
–
106
No
voltage
Dry contact for
compressor status
signal
●
●
●
Max voltage
230V Max
current 2A
107
–
108
No
voltage
Dry contact for enabling
cold water recovery
pump (if not installed on
the unit)
●
Max voltage
230V Max
current 2A
107
–
108
No
voltage
Dry contact for enabling
cold water source pump
(if not installed on the
unit)
●
Max voltage
230V Max
current 2A
110 -
109
No
voltage
Dry contact for enabling
secondary hydraulic
circuit water pump
●
●
●
Max voltage
230V
Max current 2A
142 -
143
No
voltage
Dry contact for enabling
antilegionella function
●
●
●
ANALOG INPUTS
Type of
connection by
installer
Terminal
numbers
Voltage on
the termina
ls
Meaning
A/W
A/W with
CW recove
ry
W/W
NTC probe
10kOhm at
25°C Beta
3435
39 - 32
No voltage
Analog input for BT1
probe double probe
function
●
●
●
NTC
probe 10kOh
m at 25°C
Beta 3435
40
– 32
No voltage
Analog input for BT2
probe double probe
function
●
●
●
NTC probe
10kOhm at
68 - 59
No voltage Analog input for BT3
secondary hydronic
●
●
●