Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
78
of
100
8192
DI1
ON-OFF
Remote ON-OFF
●
●
●
8193
DI2
HW
Request
Hot utility request
●
●
●
8194
DI3
RW
Request
Cold utility request
●
8195
DI4
Force DF
Forced defrost
●
●
8196
DI5
HP Switch High pressure switch
●
●
●
8197
DI6
--
Not used
●
●
●
8198
DI7
Cmp Therm Compressor thermal switch
●
●
●
8199
DI8
Oil DPres
Oil differential pressure
switch
●
●
●
8200
DI9
--
Not used
●
●
●
8201
DI10
RW Flow
sw
Recovery flow switch
●
8201
DI10
SW Flow
sw
Source flow switch
●
8202
DI11 CBrk Src
Circuit breaker source
fan/pump
●
●
●
8203
DI12 Cmp state Compressor return ON
●
●
●
9898
ExDI1 CBrk 2Pmp
Circuit breaker secondary
pump
●
●
●
9899
ExDI2 SEC
Outlet water thermal switch
●
●
●
9900
ExDI3 HWout
Defrost heaters thermal
switch
●
●
8.9.14. MENU - Bd Digital Outputs
Modbus
address Code
Description Meaning
A/W
A/W with CW
recovery
W/W
8528
DO1
Compressor
Compressor
●
●
●
8529
DO2
Oil Heater
Compressor crankcase heater
●
●
●
8530
DO3
Oil Valve
Oil valve
●
●
●
8531
DO4
HW Pump
Utility hot water pump
●
●
●
8532
DO5
RW Pump
Recovery pump
●
8532
DO5
SW Pump