Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
87
of
100
16644 RW
AI06
Anti-freeze alarm
enabling
0
1
0 = OFF
1 = ON
●
●
●
16642 RW
AI07
Hot water side anti-
freezealarm: alarm
activation set point
-15 10
°C
●
●
●
16643 RW
AI08
Hot water side anti-
freeze alarm: alarm
activation
differential
0
10
°C
●
●
●
16524 RW
AI09
Cold water side
anti- freeze heaters
activation set point
(regulation onoutlet
probe)
-15 10
°C
●
●
16525 RW
AI10
Cold water side
anti- freeze heaters
activation
differential
(regulation onoutlet
probe)
0
10
°C
●
●
16822 RW
AI11
Cold water side
anti- freeze heaters
activation set point
(regulation oninlet
probe)
-15 10
°C
●
●
16823 RW
AI12
Cold water side
anti- freeze heaters
activation
differential
(regulation oninlet
probe)
0
10
°C
●
●
16820
RW
AI13
Cold water side
anti- freeze alarm
activation set point
(regulation on outlet
probe)
-15
10
°C
●
●
16821
RW
AI14
Cold water side
anti- freeze alarm
activation
differential
(regulation on
outlet probe)
0
10
°C
●
●
16824
RW
AI15
Cold water side
anti- freeze alarm
activation set point
(regulation on inlet
-15
10
°C
●
●