8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
73
of
100
Modbus
address
Read
Write
Code
Meaning
Min
Max
Unit of
measurement
16633
RW
ST02 Enables BT1 probe OFF
ON
16633
16637
RW
ST03 BT1 probe set point 20
85 / 90 * °C
16639
RW
ST04
BT1 probe
differential
1
15
°C
16641
RW
ST05 Enables BT2 probe OFF ON
16638
RW
ST06 BT2 probe set point 10
30
°C
16640
RW
ST07
BT2 probe
differential
1
15
°C
(*) the max value can be configured by parameter.
When the parameter is selected, press the OK key to edit the value in the enable/disable
windows (parameters ST02
– ST05):
•
press the UP key to set the value ON;
•
press the DOWN key to set the value OFF;
•
press the BACK key to cancel the selection and return to the Ab.Double Probe menu;
•
press the OK key to confirm the choice and return to the Ab.Double Probe menu
In the set point windows (parameters ST03
– ST06):
•
press the UP key to increase the value by 0.1°C (32.1°F);
•
long press the UP key to increase the value by 2.5°C (36.5°F);
•
press the DOWN key to reduce the value by 0.1°C (32.1°F);
•
long press the DOWN key to reduce the value by 2.5°C (36.5°F);
•
press the BACK key to close the set point screen without confirming changes;