Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
89
of
100
Parameter AI06 is used to select whether to activate the hot side anti-freeze alarm.
If parameter AI06 = 1 (ON), the external air probe or utility water inlet value (depending on
parameter AI01) is compared with the difference between the values of parameters AI07 and
AI08. With values lower than (AI07- AI08), the anti-freeze alarm is triggered, the unit is shut
down and the
icon is displayed. When the temperature rises above the value of parameter
AI07, the alarm can be reset.