Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
81
of
100
with double probe)
9623
8999
Er CWi
Recovery side inlet probe
alarm
●
●
9624
8981
Er CWo
Recovery side outlet probe
alarm
●
9612
8981
Er SWo
Source water outlet probe
error
●
9170
9170
Er EXP
Communication error with
expansion
●
9908
9908
CBrk
SecPmp
Circuit breaker secondary
pump
●
●
●
9909
9909
CBrk
SrcFan
Circuit breaker source
fan/pump
●
●
●
9906
9906
STh
HWout
Security thermostat outlet
water
●
●
●
9907
9907
STh DEF
Security thermostat defrost
resistors
●
●
9922
9919
Er BT3
Alarm outlet water
secondary pump
●
●
●
When the status of an alarm is active, it cannot be reset. When the status is resettable, it
can be reset by pressing the RESET key at the bottom of the screen.
8.9.16. Menu - D Warnings
On the main menu, with the D.WARNINGS menu selected, press the RIGHT key to access the
list of active warnings. Warnings do not prevent the unit from working but may need to be
cleared to ensure full operation of the unit. Warnings reset themselves automatically when
the cause that generated them has been cleared.
Modbus
address
Code
Meaning
A/W
A/W with CW
recovery
W/W
9142
Warnings
(visible only on the home page)
●
●
●
9141
Pr HPL High pressure below the minimum
●
●
●
9363
HW
ELH
No frost heater switch on (hot side)
●
●
●
9004
CW
ELH
No frost heater switch on (cold side)
●
●