Lync AEGIS Controller
8: APPENDIX D
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
91
of
100
16124 R/W
MD01 RS485 no. 1 - Address 1
255
16125 R
MD02 RS485 no. 1 -
Protocol
3
4
3 = Modbus/RTU
4 = BACnet MS/TP
16126 R
MD03 RS485 no. 1 - Data bit 8
8
16127 R/W
MD04 RS485 no. 1 - Stop bit 1
2
16128
R/W
MD05
RS485 no. 1 - Parity
0
2
0 = None
1 = Odd
2 = Even
16129
R/W
MD06
RS485 no. 1
– Baud
rate
0
5
0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 76800
5 = 115200
Select the different parameters with the UP and DOWN keys. Once the parameter has been
selected, press the OK key to edit the parameter.
When the parameter is in edit mode:
•
press the UP key to increase the value;
•
press the DOWN key to decrease the value;
•
press the BACK key to select the left box;
•
press the RIGHT key to select the right box;
•
press the OK key to exit the parameter’s edit mode.
The controller must be restarted in order for the changes to take effect. Once the settings have
been changed, reboot the controller (switch it off and back on) to set the values.
The Modbus parameters can be changed in the Modbus tab of the Service menu. For Modbus
parameter changes to take effect, the controller must be restarted.
The layout of the terminals for the two serial boards is shown in the figure below.
The connections are made in the terminal block of the machine’s electrical control panel.