Lync AEGIS Controller
2: USER OPERATION VIA TOUCH SCREEN
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
20
of
100
1.
Domestic hot water temperature set point
2.
Enable temp. probe on the first (coldest) tank
3.
Setpoint of the temp. probe on the first (coldest) tank
4.
Enable the temp. probe on the last (hottest) tank
5.
Set point of the temp. probe on the last (hottest) tank
6.
Temperature differential band of the probe on the second tank
Please note that the “Hot water set point” doesn’t directly influence the compressor ON/OFF
status. The delivery temperature is regulated by modulating the primary side pump, therefore the
flow of hot water at the outlet is not constant.
If the outlet temperature probe is below the set point the pump speed is decreased, while above
the set temperature is increased.