3.3.2. Fixed Mode
This phase begins once Tevap<DF02.
A counter starts: every time Tevap>DF02, the counter resets.
When the counter reaches DF06, “Enter phase” finishes.
3.3.3. Dynamic Mode
This phase begins once Tevap<“Entering threshold”, related to the outside air temperature.
A counter starts:
every time Tevap> “Entering threshold”, the counter stops.
When the counter reaches DF06, “Entering phase” finishes.
In central phase the electrical heaters on the evaporator are activated.
There are 3 possible exit condition for the defrost central phase:
•
Pevap>DF09 for time DF08.