Using the cool recovery option, heat can be drawn from a water stream rather than the ambient
air, thus providing cooling to a water loop. This can be used to not only increase the performance
of the heat pump, but also increase the performance of water loops such as a central chilled water
system.
The function must be enabled (parameter CR01). The cooling request must be enabled via digital
input (DI03). Once these two conditions are met, the controller checks the inlet water temperature
in the recovery heat exchanger.
3.1.9. Input/Outputs
The input/output values are visible in the
Input/Output menu. The I/O mappings depend
on the unit type. Please note that the values are
updated every 3 seconds.
The unit of measure is selectable in the Service
menu (see later) between °C/bar and °F/psi.