Lync AEGIS Controller
3: USER OPERATION VIA WEB INTERFACE
L-OMM-013_A
• 4/20/2022Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
43
of
100
3.5. Logger
In order to use the datalogging function the SD card needs to be inserted in the controller, the
Enable log needs to be ON and Log cycle set. The SD card is automatically detected at unit
startup; however a manual mount request can be performed.
3.6. Polynomial
In this menu it is possible to enable the Polynomial function that is used for the calculation of the
optimal high pressure set taking in account the following physical quantities:
•
Inlet water
•
Outlet water
•
Evaporating temperature
The result is a high pressure set which will be managed by the thermostatic valve.
The set point value is in any case limited between a fixed minimum and maximum. Within these
limit values, a compensation curve based on the evaporation temperature is also active which
keeps the compressor within the envelope declared by the manufacturer.