Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
42
of
196
Figure 2.3.2.2.1-2: BST Manager
– SH & DHW: DHW Priority Screen
2. The
SH Operating Mode
screen appears. Choose the desired
Operating Mode
for the
Space Heating application, then press
Next
to continue.
Figure 2.3.2.2.1-3: BST Manager
– SH & DHW: SH Operating Mode Screen
NOTES:
•
If the outdoor air sensor is not connected, the
OAT
(Outdoor Air Temperature) parameter
is disabled.
•
If the header sensor is not connected, the bottom of the screen
will display
HDR = --- °F
.
For the header sensor to function without previous setup, the default for HDR sensor must
be sensor enabled and the source is
Direct
. For information on adjusting the defaults see
3. If you chose
Constant Setpoint
in Step 2, specify the
SH Setpoint
.
When you press
Next
the
DHW Operating Mode
screen appears (skip to Step 6, below).
Figure 2.3.2.2.1-4: BST Manager
– SH & DHW: Space Heating Constant Setpoint